Features of the XLt Operator Interface include:
- 160x128 sunlight readable graphics display
- high resolution resistive touchscreen
- 4 function keys and a system key
- (2) RS-232/485 ports support RTU/Modbus Master/Slave, ASCII In/Out, and PLC/Drive downloadable protocols
- integrated CsCAN port
- Removable Mass Storage device
- CANopen Master/Slave Support (available as a field installable firmware update, this removes CsCAN support)
| HE-XT100 | XLt Series OCS without I/O |
| HE-XT102 | XLt
Series OCS with DC/Relay I/O. Twelve (12) Digital Inputs compatible
with 12V/24VDC - four inputs can be used for 10kHz High Speed Counting.
Six (6) Relay Outputs - up to 5A continuous current. Four (4) 10-bit
Analog Inputs selectable between 0-10V and 4-20mA. |
| HE-XT103 | XLt
Series OCS with DC/DC I/O. Twelve (12) Digital Inputs compatible with
12V/24VDC - four inputs can be used for 10kHz High Speed Counting.
Twelve (12) DC Outputs - 0.5A per point - Two (2) outputs can be used
as PWM/pulse outputs. Two (2) 10-bit Analog Inputs selectable between
0-10V and 4-20mA. |
| HE-XT104 | XLt Series OCS with
High-density DC/DC I/O. Twenty-four (24) Digital Inputs compatible with
12V/24VDC - four inputs can be used for 10kHz High Speed Counting.
Sixteen (16) DC Outputs - 0.5A per point - Two (2) outputs can be used
as PWM/pulse outputs. Two (2) 10-bit Analog Inputs selectable between
0-10V and 4-20mA. |
| HE-XT105 | XLt Series OCS with
DC/DC and Universal Analog I/O. Twelve (12) Digital Inputs compatible
with 12V/24VDC - four inputs can be used for 10kHz High Speed Counting.
Twelve (12) DC Outputs - 0.5A per point - Two (2) outputs can be used
as PWM/pulse outputs. Two (2) 14-bit Universal Analog Inputs selectable
between Thermocouple, RTD, 0-100mV, 0-10V and 4-20mA. Two (2) 12-bit
Analog Outputs selectable between 0-10V and 4-20mA. |
| HE-XT106 | XLt
Series OCS with DC/DC and Universal Analog I/O. Twelve (12) Digital
Inputs compatible with 12V/24VDC - four (4) inputs can be used for 10kHz
High Speed Counting. Twelve (12) DC Outputs - 0.5A per point - Two (2)
outputs can be used as PWM/pulse outputs. Six (6) 14-bit Universal
Analog Inputs selectable between Thermocouple, RTD, 0-60mV, 0-10V and
4-20mA. Four (4) 12-bit Analog Outputs selectable between 0-10V and
4-20mA. *Operating Temp (-20°C to 60°C) For quoted T/C specs (0°C to
50°C). Storage Temp (-30°C to 70°C) and humidity 5-95% RH
non-condensing. |
Controller
| Digital I/O | High Speed In | High Speed Out | Analog In | Analog Out | Temperature In | CANbus |
| HE-XT100 | -- | -- | -- | -- | -- | -- | 1 port |
| HE-XT102 | 12/6 Relay | 4 @ 10kHz | -- | 4 10-bit | -- | -- | 1 port |
| HE-XT103 | 12/12 | 4 @ 10kHz | 2 PWM | 2 10-bit | -- | -- | 1 port |
| HE-XT104 | 24/16 | 4 @ 10kHz | 2 PWM | 2 10-bit | -- | -- | 1 port |
| HE-XT105 | 12/12 | 4 @ 10kHz | 2 PWM | 2 14/16-bit | 2 12-bit | Thermocouple, RTD | 1 port |
| HE-XT106 | 12/12 | 4 @ 10kHz | 2 PWM | 6 14/16-bit | 4 12-bit | Thermocouple, RTD | 1 port |
Special Order (*)
| Part Number | Description |
| -10 (part # extension) | Thermistor
option. Add -10 to the part number for Thermistor support for Analog
Inputs 1 & 2. (Models 102, 103, and 104 only) |
| -14 (part # extension) | Thermistor option. Add -14 to the part number for Thermistor support for Analog Inputs 1, 2, 3 & 4 (Model 102 only) |
| -22 (part # extension) | Display Heater tested at (-40°C) (Not valid for Model 106) |
| -33 (part # extension) | DeviceNet
Option. Add -33 part number extension for DeviceNet communications
(Polled & Explicit Connections only). CsCAN support is removed. |
| -44 (part # extension) | SAE J1939 Option. Add -44 part number extension for SAE J1939 communications. CsCAN support is removed. |
| -200 (part # extension) | CAN Open Firmware pre-loaded. CsCAN support is removed. |
|